Title page for ETD etd-04192006-193202


Type of Document Dissertation
Author Xu, Chunchun
URN etd-04192006-193202
Title High Accuracy Real-time GPS Synchronized Frequency Measurement Device for Wide-area Power Grid Monitoring
Degree PhD
Department Electrical and Computer Engineering
Advisory Committee
Advisor Name Title
Liu, Yilu Committee Chair
Centeno, Virgilio A. Committee Co-Chair
Conners, Richard W. Committee Member
Hsiao, Michael S. Committee Member
Liang, Yao Committee Member
Lin, Tao Committee Member
Keywords
  • Frequency Disturbance Recorder
  • Real-time Embedded System Design
  • Power System Frequency Tracking
  • GPS
  • FNET
  • Frequency Monitoring Network
  • FDR
  • Wide-area Measurement System
Date of Defense 2006-02-20
Availability unrestricted
Abstract

Frequency dynamics is one of the most important signals of a power system, and it is an indicator of imbalance between generation and load in the system. The Internet-based real-time GPS-synchronized wide-area Frequency Monitoring Network (FNET) was proposed to provide imperative frequency dynamics information for a variety of system-wide monitoring, analysis and control applications. The implementation of FNET has for the first time made the synchronized observation of the entire U.S. power network possible with very little cost.

The FNET is comprised of many Frequency Disturbance Recorders (FDR) geographically dispersed throughout the U.S. and an Information Management System (IMS), currently located at Virginia Tech. The FDR works as a sensor, which performs local measurements and transmits calculations of frequency, voltage magnitude and voltage angle to the remote servers via the Internet. Compared with its commercial counterpart Phasor Measurement Unit (PMU), FDR provides less expensive version for networked high-resolution real-time synchronized. The improved single phase algorithm in the FDRs made it possible to measure at 110V level which is much more challenging than PMUs due to the noise involved at this level.

This research work presents the challenges and issues of both software and hardware design for the novel measurement device FDR, which is one of the devices with the highest dynamic precision for power system frequency measurement. The DFT-based Phasor Angle Analysis algorithm has been improved to make sure the high-resolution measuring FDRs are installed at residential voltage outlets, instead of substation high-voltage inputs. An embedded 12-channel timing GPS receiver has been integrated to provide an accurate timing synchronization signal, UTC time stamp, and unit location. This research work also addresses the harmonics, voltage swing and other noise components' impacts on the measurement results, and the optimized design of filters and a coherent sampling scheme to reduce or eliminate those impacts. The verification test results show that the frequency measurement accuracy of the FDR is within +/-0.0005Hz, and the time synchronization error is within +/-500ns with suitable GPS antenna installation. The preliminary research results show the measurement accuracy and real-time performance of the FDR are satisfactory for a variety of FNET applications, such as disturbance identification and event location triangulation.

Files
  Filename       Size       Approximate Download Time (Hours:Minutes:Seconds) 
 
 28.8 Modem   56K Modem   ISDN (64 Kb)   ISDN (128 Kb)   Higher-speed Access 
  XuChunchunVTETD.pdf 1.82 Mb 00:08:26 00:04:20 00:03:47 00:01:53 00:00:09

Browse All Available ETDs by ( Author | Department )

dla home
etds imagebase journals news ereserve special collections
virgnia tech home contact dla university libraries

If you have questions or technical problems, please Contact DLA.