Type of Document Master's Thesis Author Novak, Julia Ann Author's Email Address jnovak@vt.edu URN etd-05032005-171633 Title Cavitation and Bubble Formation in Water Distribution Systems Degree Master of Science Department Environmental Engineering Advisory Committee
Advisor Name Title Edwards, Marc A. Committee Chair Diplas, Panayiotis Committee Member Loganathan, G. V. Committee Member Keywords
- Gaseous Cavitation
- Bubbles
- Corrosion
- Dissolved Gas
Date of Defense 2005-04-08 Availability restricted Abstract Gaseous cavitation is examined from a practical and theoretical standpoint. Classical cavitation experiments which disregard dissolved gas are not directly relevant to natural water systems and require a redefined cavitation inception number which considers dissolved gases. In a pressurized water distribution system, classical cavitation is only expected to occur at extreme negative pressure caused by water hammer or at certain valves. Classical theory does not describe some practical phenomena including noisy pipes, necessity of air release valves, faulty instrument readings due to bubbles, and reports of premature pipe failure; inclusion of gaseous cavitation phenomena can better explain these events. Gaseous cavitation can be expected to influence corrosion in water distribution pipes.
Bubbles can form within the water distribution system by a mechanism known as gaseous cavitation. A small scale apparatus was constructed to track gaseous cavitation as it could occur in buildings. Four independent measurements including visual observation of bubbles, an inline turbidimeter, an ultrasonic flow meter, and an inline total dissolved gas probe were used to track the phenomenon. All four measurements confirmed that gaseous cavitation was occurring within the experimental distribution system, even at pressures up to 40 psi. Gaseous cavitation was more likely at higher initial dissolved gas content, higher temperature, higher velocity and lower pressure. Certain changes in pH, conductivity, and surfactant concentration also tended to increase the likelihood of cavitation. For example, compared to the control at pH 5.0 and 30 psig, the turbidity increased 295% at pH 9.9. The formation of bubbles reduced the pump’s operating efficiency, and in the above example, the velocity was decreased by 17% at pH 9.9 versus pH 5.0.
Files
Filename Size Approximate Download Time (Hours:Minutes:Seconds)
28.8 Modem 56K Modem ISDN (64 Kb) ISDN (128 Kb) Higher-speed Access Thesis.pdf 1.60 Mb 00:07:23 00:03:48 00:03:19 00:01:39 00:00:08 indicates that a file or directory is accessible from the Virginia Tech campus network only.
If you have questions or technical problems, please Contact DLA.