Title page for ETD etd-08182005-105558


Type of Document Dissertation
Author Zhong, Zhian
Author's Email Address zzhong@vt.edu
URN etd-08182005-105558
Title Power Systems Frequency Dynamic Monitoring System Design and Applications
Degree PhD
Department Electrical and Computer Engineering
Advisory Committee
Advisor Name Title
Liu, Yilu Committee Chair
Centeno, Virgilio A. Committee Co-Chair
Conners, Richard W. Committee Member
Liang, Yao Committee Member
Lin, Tao Committee Member
Keywords
  • Phasor Measurement Unit (PMU)
  • Under Frequency Load Shedding
  • Wide Area Measurement System
  • Frequency Monitoring Network (FNET)
  • Frequency Disturbance Recorder (FDR)
  • GPS
Date of Defense 2005-07-29
Availability unrestricted
Abstract
Recent large-scale blackouts revealed that power systems around the world are far from the stability and reliability requirement as they suppose to be. The post-event analysis clarifies that one major reason of the interconnection blackout is lack of wide area information. Frequency dynamics is one of the most important parameters of an electrical power system. In order to understand power system dynamics effectively, accurately measured wide-area frequency is needed. The idea of building an Internet based real-time GPS synchronized wide area Frequency Monitoring Network (FNET) was proposed to provide the imperative dynamic information for the large-scale power grids and the implementation of FNET has made the synchronized observations of the entire US power network possible for the first time. The FNET system consists of Frequency Disturbance Recorders (FDR), which work as the sensor devices to measure the real-time frequency at 110V single-phase power outlets, and an Information Management System (IMS) to work as a central server to process the frequency data. The device comparison between FDR and commercial PMU (Phasor Measurement Unit) demonstrate the advantage of FNET. The web visualization tools make the frequency data available for the authorized users to browse through Internet.

The research work addresses some preliminary observations and analyses with the field-measured frequency information from FNET. The original algorithms based on the frequency response characteristic are designed to process event detection, localization and unbalanced power estimation during frequency disturbances. The analysis of historical cases illustrate that these algorithms can be employed in real-time level to provide early alarm of abnormal frequency change to the system operator. The further application is to develop an adaptive under frequency load shedding scheme with the processed information feed in to prevent further frequency decline in power systems after disturbances causing dangerous imbalance between the load and generation.

Files
  Filename       Size       Approximate Download Time (Hours:Minutes:Seconds) 
 
 28.8 Modem   56K Modem   ISDN (64 Kb)   ISDN (128 Kb)   Higher-speed Access 
  Dissertation-0824-submittion.pdf 3.97 Mb 00:18:21 00:09:26 00:08:15 00:04:07 00:00:21

Browse All Available ETDs by ( Author | Department )

dla home
etds imagebase journals news ereserve special collections
virgnia tech home contact dla university libraries

If you have questions or technical problems, please Contact DLA.