Type of Document Dissertation Author Ghassemian, Alireza Author's Email Address aghassem@vt.edu URN etd-91497-135743 Title Robust Statistical Methods for Measurement calibration in Large Electric Power Systems Degree PhD Department Electrical Engineering Advisory Committee
Advisor Name Title Mili, Lamine M. Committee Chair Beex, A. A. Louis Committee Member Broadwater, Robert P. Committee Member Coakley, Clint W. Committee Member Liu, Y. A. Committee Member Mili, Lamine M. Committee Member Keywords
- Robust statistic
- Measurement calibration
Date of Defense 1997-10-13 Availability restricted Abstract The Objective of the Remote Measurements Calibration (RMC)method is to minimize systematic errors through an
appropriate scaling procedure. A new method for RMC has
been developed. This method solves the problems of
observability, multiplicity of solutions, and ambiguity of
reference points associated with the method proposed by
Adibi et. al. [6-9]. The new algorithm uses the simulated
annealing technique together with the matroid method to
identify and minimize the number of RTUs (Remote Terminal
Units) required to observe the system. After field
calibration, these RTUs provide measurements that are used
to estimate the whole state of the system. These estimates
are then returned as a reference for remotely calibrating
the remaining RTUs. The calibration coefficients are
estimated by means of highly robust estimator, namely the
Least Median of Squares (LMS) estimator. The calibration
method is applicable to large systems by means of network
tearing and dynamic programming. The number of field
calibrations can be decreased further whenever multiple
voltage measurements at the same buses are available. The
procedure requires that the measurement biases are estimated
from recorded metered values when buses, or lines, or
transformers are disconnected. It also requires the
application of a robust comparative voltage calibration
method. To this end, a modified Friedman test has been
developed and its robustness characteristics investigated.